EasyManuals Logo

Omron E5AN User Manual

Omron E5AN
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
70
Alarm Outputs Section 3-9
Note (1) With set values 1, 4, and 5, the upper- and lower-limit values can be set
independently for each alarm type, and are expressed as “L” and “H.
(2) Set value: 1 (Upper- and lower-limit alarm)
(3) Set value: 4 (Lower limit range)
(4) Set value: 5 (Upper- and lower-limit with standby sequence)
For the lower-limit alarms in cases 1 and 2 above, the alarm is always
OFF if upper- and lower-limit hysteresis overlaps.
In case 3, the alarm is always OFF.
3 Lower-limit Set the downward deviation in the
set point by setting the alarm value
(X).
4 (See note
1.)
Upper- and lower-limit
range
See note 3. Set the deviation in the set point by
setting the alarm upper limit (H)
and alarm lower limit (L).
5 (See note
1.)
Upper- and lower-limit
with standby sequence
See note 4. A standby sequence is added to
the upper- and lower-limit alarm
(1). (See note 6.)
6 Upper-limit with standby
sequence
A standby sequence is added to
the upper-limit alarm (2). (See note
6.)
7 Lower-limit with standby
sequence
A standby sequence is added to
the lower-limit alarm (3). (See note
6.)
8 Absolute-value upper-
limit
The alarm will turn ON if the pro-
cess value is larger than the alarm
value (X) regardless of the set
point.
9 Absolute-value lower-limit The alarm will turn ON if the pro-
cess value is smaller than the
alarm value (X) regardless of the
set point.
10 Absolute-value upper-
limit with standby
sequence
A standby sequence is added to
the absolute-value upper-limit
alarm (8). (See note 6.)
11 Absolute-value lower-limit
with standby sequence
A standby sequence is added to
the absolute-value lower-limit
alarm (9). (See note 6.)
12 LBA (alarm 1 type only) --- Refer to page 118. (See note 7.)
13 PV change rate alarm --- Refer to page 72. (See note 8.)
Set value Alarm type Alarm output operation Description of function
When alarm value X
is positive
When alarm value X
is negative
X
ON
OFF
SP
X
ON
OFF
SP
LH
ON
OFF
SP
LH
ON
OFF
SP
See note 5.
X
ON
OFF
SP
ON
OFF
SP
X
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
0
X
ON
OFF
0
ON
OFF
X
0
ON
OFF
X
0
X
ON
OFF
0
X
ON
OFF
0
ON
OFF
X
0
ON
OFF
X
0
LH
H < 0, L > 0
|H| < |L|
SP
LH
H > 0, L < 0
|H| > |L|
SP
LH
H < 0, L < 0
SP
LH
H < 0, L > 0
|H| |L|
SP
LH
H > 0, L < 0
|H| |L|
SP
Case 1 Case 2 Case 3 (Always ON)
LH
H < 0, L > 0
|H| < |L|
SP
HL
H > 0, L < 0
|H| > |L|
SP
LH
H < 0, L <
0
SP
L
L
H
H
H < 0, L > 0
|H| |L|
SP
SP
H > 0, L < 0
|H| |L|
Case 1
Case 2 Case 3 (Always OFF)

Table of Contents

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals