Using Event Inputs Section 4-5
Two set points are set externally by using the Number of Multi-SP Uses
parameter.
Switching is possible between two set points (0 and 1) by setting the
Number of Multi-SP Uses parameter to 1. The default setting is 1 and
does not need to be changed to switch between two set points. Set points
0 and 1 are specified by the status of event input 1.
4-5-2 How to Use the Multi-SP Function
The multi-SP function allows you to set up to four set points (SP 0 to 3) in the
adjustment level. The set point can be switched by operating the keys on the
front panel or by using external input signals (event inputs).
Using Event Inputs
Two Event Inputs: Event Inputs 1 and 2
The following tables show the relationship between the ON/OFF combinations
of event inputs 1 and 2 and the selected set points.
Number of Multi-SP Uses = 1
Number of Multi-SP Uses = 2
Using Key Operations You can select any of the set points 0 to 3 by changing the set value of the
Multi-SP Uses parameter. The Multi-SP Uses parameter display conditions
are as follows:
If the Controller does not support event inputs, the Multi-SP Uses param-
eter must be set to ON.
If the Controller supports event inputs, the Number of Multi-SP Uses
parameter must be set to 0 and the Multi-SP Uses parameter must be set
to ON.
E5CN
E5GN
EV1
EV2
EV1
EV2
+
+
EV1
EV2
EV1
EV2
+
+
E5AN/EN
11
12
13
11
12
13
E53-CN@B@N2 in the
E5CN-@M@-500 (for E5CN)
E53-AKB in the E5AN/EN-@M@-500-N
(for E5AN/EN)
+
+
EV1
EV2
EV1
EV2
7
8
9
Event input 1 Selected set point
OFF Set point 0
ON Set point 1
Event input 1 Event input 2 Selected set point
OFF OFF Set point 0
ON OFF Set point 1
OFF ON Set point 2
ON ON Set point 3