Adjustment Level Section 5-4
• This parameter enables/disables writing of parameters to the E5CN from
the host (personal computer) using communications.
• This parameter is not displayed if communications write enable/disable is
set for execution using an event input assignment 1 and 2.
ON: Writing enabled
OFF: Writing disabled
• Default: OFF
â–  Related Parameters
MB command logic switching (advanced function setting level): Page 229
Communications Unit No., Communications baud rate, Communications data
length, Communications parity, Communications stop bits (communications
setting level): Page 255
This parameter measures the heater current from the CT input used for
detecting heater burnout.
This parameter measures and displays the heater current value.
• Heater burnouts or heater overcurrent are not detected if the control out-
put (heating) ON time is 100 ms or less.
• ffff is displayed when 55.0 A is exceeded.
• If a heater burnout detection 1 or heater overcurrent detection 1 alarm is
output, the HA indicator will light and the No. 1 display for the heater cur-
rent 1 value monitor will flash.
â–  Related Parameters
Heater burnout detection 1, Heater burnout detection 2 (adjustment level):
Pages 181, and 183
HB ON/OFF (advanced function setting level): Page 222
Heater overcurrent detection 1, Heater overcurrent detection 2 (adjustment
level): Pages 181, and 183
Heater overcurrent use (advanced function setting level): Page 246
Error displays ct1: Page 283
cmwt Communications Writing
Communications must be supported.
The Event Input Assignments 1 and
2 parameters must not be set to
enable communications writing.
Function
Setting
See
See
ct1 Heater Current 1 Value Monitor
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The HB ON/OFF parameter or
Heater Overcurrent Use parameter
must be set to ON.
Monitor range Unit
0.0 to 55.0 A
Function
Monitor
See
See

Table of Contents

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals