Adjustment Level Section 5-4
This parameter sets the time for the control operation when using the sim-
ple program function.
Related Parameters
Program start, Soak time remain (operation level): Page 171
Wait band (adjustment level): Page 191
Program pattern (initial setting level): Page 205
Soak time unit (advanced function setting level): Page 243
This parameter sets the stable band within which the soak time is mea-
sured for the simple program function.
Note Set “None” as the unit for Controllers with Analog Inputs.
Related Parameters
Program start, Soak time remain (operation level): Page 171
Soak time (adjustment level): Page 191
Program pattern (initial setting level): Page 205
Soak time unit (advanced function setting level): Page 243
soak Soak Time
The Program Pattern parameter
must not be set to OFF.
Setting range Unit Default
1 to 9999 min or h 1
Function
Setting
See
See
wt-b Wait Band
The Program Pattern parameter
must not be set to OFF.
Model Setting range Unit Default
Controllers with Thermocouple/Resis-
tance Thermometer Universal Inputs
OFF or 0.1 to
999.9
°C or °F
(See note.)
off
Controllers with Analog Inputs OFF or 0.01 to
99.99
%FS
Function
Setting
See
See

Table of Contents

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals