Advanced Function Setting Level Section 5-8
Alarm 1, 2, or 3 outputs are prevented from turning ON until after the delay
times set in these parameters have elapsed.
Set the time for which the ON delay is to be enabled.
To disable the ON delay, set 0.
Related Parameters
Alarm 1 to 3 type (initial setting level): Pages 207 to 210
Alarm 1, 2, or 3 outputs are prevented from turning OFF until after the delay
times set in these parameters have elapsed.
Set the time for which the OFF delay is to be enabled.
To disable the OFF delay, set 0.
Related Parameters
Alarm 1 to 3 type (initial setting level): Pages 207 to 210
a1on Alarm 1 ON Delay
Alarm 1 must be assigned, and the
alarm 1 type must not be 0, 12, or
13.
a2on Alarm 2 ON Delay
Alarm 2 must be assigned, and the
alarm 2 type must not be 0, 12, or
13.
a3on Alarm 3 ON Delay
Alarm 3 must be assigned, and the
alarm 3 type must not be 0, 12, or
13.
Setting range Unit Default
0 to 999 Second 0
Function
Setting
See
See
a1of Alarm 1 OFF Delay
Alarm 1 must be assigned, and the
alarm 1 type must not be 0, 12, or
13.
a2of Alarm 2 OFF Delay
Alarm 2 must be assigned, and the
alarm 2 type must not be 0, 12, or
13.
a3of Alarm 3 OFF Delay
Alarm 3 must be assigned, and the
alarm 3 type must not be 0, 12, or
13.
Setting range Unit Default
0 to 999 Second 0
Function
Setting
See
See