Advanced Function Setting Level Section 5-8
Set this parameter to use HS alarms.
When this parameter is set to ON, the HS alarm is held until any of the fol-
lowing conditions is satisfied.
a The HS alarm current is set to 50.0 A.
b The power is cycled.
c The latch is cancelled by the PF Key.
(PF Setting = LAT: Alarm Latch Cancel)
d The latch is cancelled by an event input.
(Event Input Assignment 1 and 2 = LAT: Alarm Latch Cancel)
Output is turned OFF when switching to the initial setting level, communi-
cations setting level, advanced function setting level, or calibration level.
Related Parameters
HS alarm use (advanced function setting level): Page 235
Event input assignment 1 and 2 (initial setting level): Page 216
HB ON/OFF: Page 222, PF setting: Page 247 (advanced function setting
level)
hsu HS Alarm Use
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
Setting range Default
on: Enabled, off: Disabled on
Function
Setting
hsl HS Alarm Latch
Heater burnout, HS alarms, and
heater overcurrent detection must be
supported.
Alarm 1 must be assigned.
The HS Alarm parameter must be
set to ON.
Setting range Default
on: Enabled, off: Disabled OFF
Function
Setting