238
Advanced Function Setting Level Section 5-8
This parameter sets the function to be assigned to control output 1.
Note (1) If c-o is assigned for standard control, a value equivalent to 0% is output.
(2) Can be selected for relay and voltage outputs (for driving SSR) only.
(3) Can be selected when the Program Pattern parameter is set to OFF, but
the function will be disabled.
(4) WR1 to WR8 are not displayed when the logic operation function is not
used.
Related Parameters
Standard or heating/cooling: Page 204, Program pattern: Page 205, Transfer
output type: Page 210 (initial setting level)
out1 Control Output 1 Assignment
The transfer output type must be set
to OFF when the control output is a
current output.
Setting range Default
None: No function is assigned to control output 1. o
o: Heating control output is output.
c-o: Cooling control output is output. (See note 1.)
alm1: Alarm 1 is output. (See note 2.)
alm2: Alarm 2 is output. (See note 2.)
alm3: Alarm 3 is output. (See note 2.)
p.end: Program end is output. (See notes 2 and 3.)
ralm: Control output ON/OFF count alarm (See note 2.)
wr1: Work bit 1 (See notes 2 and 4.)
wr2: Work bit 2 (See notes 2 and 4.)
wr3: Work bit 3 (See notes 2 and 4.)
wr4: Work bit 4 (See notes 2 and 4.)
wr5: Work bit 5 (See notes 2 and 4.)
wr6: Work bit 6 (See notes 2 and 4.)
wr7: Work bit 7 (See notes 2 and 4.)
wr8: Work bit 8 (See notes 2 and 4.)
Function
Setting
See
See