EasyManua.ls Logo

Omron E5AN

Omron E5AN
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
289
Appendix
Adjustment Level
Parameters Characters Setting (monitor) value Display Default Unit Set value
Adjustment Level
Display
l.adj
AT Execute/Cancel at OFF, AT Cancel
AT-2: 100%AT Execute
AT-1: 40%AT Execute
off,
at-2,
at-1
OFF None
Communications
Writing
cmwt OFF, ON off, on OFF None
Heater Current 1
Value Monitor
ct1 0.0 to 55.0 A
Heater Burnout
Detection 1
hb1 0.0 to 50.0 0.0 A
Heater Overcurrent
Detection 1
oc1 0.0 to 50.0 50.0 A
Heater Current 2
Value Monitor
ct2 0.0 to 55.0 A
Heater Burnout
Detection 2
hb2 0.0 to 50.0 0.0 A
Heater Overcurrent
Detection 2
oc2 0.0 to 50.0 50.0 A
Leakage Current 1
Monitor
lcr1 0.0 to 55.0 A
HS Alarm 1 hs1 0.0 to 50.0 50.0 A
Leakage Current 2
Monitor
lcr2 0.0 to 55.0 A
HS Alarm 2 hs2 0.0 to 50.0 50.0 A
SP 0 sp-0 SP lower limit to SP upper
limit
0EU
SP 1 sp-1 SP lower limit to SP upper
limit
0EU
SP 2 sp-2 SP lower limit to SP upper
limit
0EU
SP 3 sp-3 SP lower limit to SP upper
limit
0EU
Temperature Input
Shift
ins 199.9 to 999.9 0.0 °C or °F
Upper Limit Temper-
ature Input Shift
Value
insh 199.9 to 999.9 0.0 °C or °F
Lower Limit Temper-
ature Input Shift
Value
insl 199.9 to 999.9 0.0 °C or °F
Proportional Band p Universal input: 0.1 to 999.9 8.0 °C or °F
(See note
1.)
Analog input: 0.1 to 999.9 10.0 %FS
Integral Time i 0 to 3,999 233 Second
Derivative Time d RT OFF: 0 to 3,999 40 Second
RT ON: 0.0 to 999.9 40.0 Second
Cooling Coefficient c-sc 0.01 to 99.99 1.00 None
Dead Band c-db Universal input: 199.9 to
999.9
0.0 °C or °F
(See note
1.)
Analog input: 19.99 to 99.99 0.00 %FS

Table of Contents