5 Communications Data for Modbus
E5@C Digital Temperature Controllers Communications Manual (H175)
5-1 Variable Area (Setting Range) List
5
Address
Parameter name Setting (monitor) value Level
Four-byte
mode
Two-byte
mode
1302 3301 SP Tracking H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
1308 3304 PV Dead Band H'00000000 to H'0000270F (0 to 9999)
130A 3305 Cold Junction
Compensation Method
H'00000000 (0): OFF
H'00000001 (1): ON
1312 3309 Integral/Derivative Time
Unit
H'00000000 (0): 1 s
H'00000001 (1): 0.1 s
1314 330A α H'00000000 to H'00000064 (0.00 to 1.00)
1318 330C Manual Output Method H'00000000 (0): HOLD
H'00000001 (1): INIT
131A 330D Manual MV Initial Value Standard control or close position-proportional control:
H'FFFFFFCE to H'0000041A (−5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (−105.0 to 105.0)
131E 330F AT Calculated Gain H'00000001 to H'00000064 (0.1 to 10.0)
1320 3310 AT Hysteresis H'00000001 to H'0000270F (0.1 to 999.9 for temperature input)
H'00000001 to H'000003E7 (0.01 to 9.99 for analog input)
1322 3311 Limit Cycle MV Amplitude H'00000032 to H'000001F4 (5.0 to 50.0)
1328 3314 Heater Burnout Latch H'00000000 (0): OFF
H'00000001 (1): ON
132A 3315 Heater Burnout
Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
132C 3316 HS Alarm Latch H'00000000 (0): OFF
H'00000001 (1): ON
132E 3317 HS Alarm Hysteresis H'00000001 to H'000001F4 (0.1 to 50.0)
1336 331B Number of Multi-SP
Points
H'00000001 (1): OFF
H'00000002 to H'00000008 (2 to 8)
1338 331C HB ON/OFF H'00000000 (0): OFF
H'00000001 (1): ON
133C 331E Integrated Alarm
Assignment
H'00000000 to H'000000FF (0 to 255)
1340 3320 MV at Stop and Error
Addition
H'00000000 (0): OFF
H'00000001 (1): ON
1342 3321 ST Stable Range H'00000001 to H'0000270F (0.1 to 999.9)
1344 3322 RT H'00000000 (0): OFF
H'00000001 (1): ON
Note: Valid only with temperature input.
1346 3323 HS Alarm Use H'00000000 (0): OFF
H'00000001 (1): ON
1348 3324 LBA Detection Time H'00000000 to H'0000270F (0 to 9999)
134A 3325 LBA Level H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
134C 3326 LBA Band H'00000000 to H'0000270F
(0.0 to 999.9 for temperature input)
(0.00 to 99.99 for analog input)
134E 3327 Soak Time Unit H'00000000 (0): Minutes
H'00000001 (1): Hours
H'00000002 (2): Seconds
*1
1350 3328 Alarm SP Selection H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
1352 3329 Remote SP Enable H'00000000 (0): OFF
H'00000001 (1): ON
1356 332B Manual MV Limit Enable H'00000000 (0): OFF
H'00000001 (1): ON
1358 332C Direct Setting of Position
Proportional MV
H'00000000 (0): OFF
H'00000001 (1): ON
135A 332D PV Rate of Change
Calculation Period
H'00000001 to H'000003E7 (1 to 999)
*1 Selection is possible only with the E5DC and E5GC. (The D5DC must be manufactured in July 2014 or later (version
2.2 or higher).)