6 Programless Communications
6 - 12
E5@C Digital Temperature Controllers Communications Manual (H175)
There are 13 upload settings and 13 download settings.
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to fins, mcp4, or fxp4.
* This parameter cannot be used when the Protocol Setting parameter is set to fxp4.
Example of Changing a Setting:
To set the Alarm Value 3 parameter for Download Setting 11, you would change the set value from 45
(Heater Burnout Detection 1) to 38 (Alarm Value 3).
6-2-8 Upload Settings and Download Settings
Parameter name Displayed characters Setting range Default
Upload Setting 1 up 1 0 to 98 1 Communications Monitor
Upload Setting 2 up 2 2 Status (Upper Word)
Upload Setting 3 up 3 3 Status (Lower Word)
Upload Setting 4 up 4 4 Status 2 (Upper Word)
Upload Setting 5 up 5 6 Decimal Point Monitor
Upload Setting 6 up 6 7 Process Value
Upload Setting 7 up 7 8 Internal Set Point
Upload Setting 8 up 8 11 Heater Current 1 Value
Monitor
Upload Setting 9 up 9 16 MV Monitor (Heating)
Upload Setting 10 up10 0 Nothing assigned.
Upload Setting 11 up11 0 Nothing assigned.
Upload Setting 12 up12 0 Nothing assigned.
Upload Setting 13* up13 0 Nothing assigned.
Download Setting 1 dn 1 30 to 98 31 Set Point
Download Setting 2 dn 2 61 Proportional Band
Download Setting 3 dn 3 62 Integral Time
Download Setting 4 dn 4 63 Derivative Time
Download Setting 5 dn 5 32 Alarm Value 1
Download Setting 6 dn 6 33 Alarm Value Upper Limit 1
Download Setting 7 dn 7 34 Alarm Value Lower Limit 1
Download Setting 8 dn 8 35 Alarm Value 2
Download Setting 9 dn 9 36 Alarm Value Upper Limit 2
Download Setting 10 dn10 37 Alarm Value Lower Limit 2
Download Setting 11 dn11 45 Heater Burnout Detection 1
Download Setting 12 dn12 57 Process Value Input Shift
Download Setting 13 dn13 75 SP Ramp Set Value

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals