2 CompoWay/F Communications Procedures
2 - 4
E5@C Digital Temperature Controllers Communications Manual (H175)
The following examples show the end code when a command did not end normally.
Example 1) Illegal Sub-address, No SID, and No Command Text
Command
Response
End code is “16” (sub-address error).
The sub-address error code is used because the sub-address error has a higher error detection
priority than the format error.
Example 2) No Command Text
Command
Response
The end code is “14” (format error).
Example 3) No Node Number Provided
Command
The node number is lacking one character.
Response
There is no response.
2-1-4 Communications Data
Communications
format
Set (monitor)
values
Negative values Decimal point
CompoWay/F 8-digit hexadecimal 2's complement Decimal point is removed and the result is
converted to hexadecimal.
Example conversion: 105.0 1050
H'0000041A
2-1-5 End Code Example
STX 0 A ETX
BCC
Node number Sub-address
A ETX
BCC
16STX 0
Node number
Sub-address
End code
STX 0 0 ETX
BCCSID
0
Node number Sub-address
0ETX
BCC
14STX 0
Node number
Sub-address
End code
STX ETX
BCC

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals