3 Communications Data for CompoWay/F
3 - 6
E5@C Digital Temperature Controllers Communications Manual (H175)
C1 (81) 002C MV Change Rate
Limit
H'00000000 to H'000003E8 (0.0 to 100.0) Adjustment
C1 (81) 002D Position
Proportional Dead
Band
H'00000001 to H'00000064 (0.1 to 10.0)
C1 (81) 002E Open/Close
Hysteresis
H'00000001 to H'000000C8 (0.1 to 20.0)
C1 (81) 002F Remote SP Input
Shift
H'FFFFF831 to H'0000270F (1999 to 9999)
C1 (81) 0030 Remote SP input
Slope Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
C1 (81) 0031 Extraction of
Square Root
Low-cut Point
H'00000000 to H'000003E8 (0.0 to 100.0)
C1 (81) 0032 Alarm Value 4 H'FFFFF831 to H'0000270F (1999 to 9999)
C1 (81) 0033 Alarm Value Upper
Limit 4
H'FFFFF831 to H'0000270F (1999 to 9999)
C1 (81) 0034 Alarm Value Lower
Limit 4
H'FFFFF831 to H'0000270F (1999 to 9999)
C1 (81) 0035 SP 4 SP lower limit to SP upper limit
C1 (81) 0036 SP 5 SP lower limit to SP upper limit
C1 (81) 0037 SP 6 SP lower limit to SP upper limit
C1 (81) 0038 SP 7 SP lower limit to SP upper limit
C1 (81) 0039 Proportional Band
(Cooling)
H'00000001 to H'0000270F (0.1 to 999.9)
C1 (81) 003A Integral Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81) 003B Derivative Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
Variable
type
Address Parameter name Setting (monitor) value Level

Table of Contents

Other manuals for Omron E5EC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5EC and is the answer not in the manual?

Omron E5EC Specifications

General IconGeneral
Mounting TypePanel Mount
Display Resolution0.1°C or 1°C
Control MethodON/OFF
Input TypeThermocouple, RTD, Analog voltage
Supply Voltage100 to 240 VAC
Output TypeRelay, Voltage, Current
Size48 x 96 mm
Control OutputRelay, Voltage, Current
Alarm OutputRelay
CommunicationRS-485
Ambient Operating Temperature-10 to 55°C
Ambient Operating Humidity25 to 85% RH
Protection RatingIP20

Related product manuals