7. Using the UPS monitoring software and contact signal
76
7-4-10. Xserve RAID connection procedure
Apple’s Xserve RAID can be controlled by changing the unit’s contact signal card settings.
* Cable: Connection cable (BUC28), sold separately
1. UPS connection procedure
(1) Turn OFF the unit’s power switch and remove the contact signal card from the rear of the unit.
- How to insert/remove the contact signal card Page 73
(2) Change the contact signal card’s JP2 to JP9 jumper settings (8 settings) to “SC05/06.”
(3) Change the JP10 jumper setting to “SC05XSR.”
(4) Insert the contact signal card into the UPS.
(5) Connect the BUC28 cable connector (female end) to the Xserve RAID serial port and turn the con-
nector fi xing screw clockwise to tighten it.
Connect the other end (male end) of the same cable to the contact signal card and turn the connec-
tor fi xing screw clockwise to tighten it.
Change Jumper settings
(9 degits)
BUC28
cable
XserveRAID
XserveRAID
XserveXserve
BU75RW/BU100RW
BU200RW/BU300RW
BUC28
cable
Contact
signal card
USB
connector
USB
cable
USB
cable
USB
connector
Contact
signal card
(6) Turn ON the power switches for the Xserve RAID and the UPS.