Loading...
3-10
Param-
eter
No.
(Regis-
ter No.
(Hex))
MemoChanges
during
opera-
tion
Default
setting
Set-
ting
range
DescriptionName
n39
(0127)
Multi-func-
tion input 4
(Input ter-
minal S5)
12 External
base block
command
(NO)
ON: Output shut off
(while motor coasting to a
stop and “bb” flashing)
2 to 8,
10 to
22,
34, 35
6 No
)
13 External
base block
command
(NC)
OFF: Output shut off
(with motor free running
and “bb” flashing)
14 Search
command
(Searching
starts from
maximum
frequency)
ON: Speed search
(Searching starts from
n09)
15 Search
command
(Searching
starts from
preset fre-
quency)
ON: Speed search
16 Accelera-
tion/Decel-
eration-pro-
hibit com-
mand
ON: Acceleration/Decel-
eration is on hold (run-
ning at parameter fre-
quency)
17 Local or re-
mote selec-
tion
ON: Local mode (oper-
ated with the Digital Op-
erator)
18 Commu-
nications or
remote
selection
ON: RS-422A/485 com-
munications input is
enabled.
OFF: The settings of n02
and n03 are enabled.
List of Parameters Chapter 3