7.3.8 Values of operating parameters
Since version V5.1, operating parameters are also accessible via Modbus output
inteface
As well as indicators, data are stored in IEEE floating format over 32 bits.
Two consecutive addresses are then required for each indicator value.
Values are stored from address 7000 equipment by equipment in the following ordrer:
1. Rot speed Address : 7000
2. DC1 Address : 7002
3. DC2 Address : 7004
4. TOR1 Address : 7006
5. TOR2 Address : 7008
6. TOR3 Address : 7010
If several machines are connected to MVX, the second is at the following address
(7012) and so on. The order can be checked in the file produced by the "Export
Excel" function of the MVX