User Manual Chapter 3
GFK-2749A Jan 2020
Configuration and Data Transfer 56
Index
(%AQ
Word 1)
Parameter Value
(%AQ Word 2)
Default value
Value Limits
46
UNDER_FRQ_DELAY (ANSI
81Ub)
100 [0.1 sec]
1 to 32767
47
OVER_FRQ_THR (ANSI 81Oa)
50 [0.01 Hz]
1 to 1000
48
OVER_FRQ_DELAY (ANSI 81Ob)
100 [0.1 sec]
1 to 32767
49
Reserved
0
NA
50
Zero / Capture / Diagnostic
0
0 to 1896
Zero Capture Diagnostic Operation
The value written to parameter index 50 selects the variable that will be written to the
Diagnostic Data word (%AI offset 60) in the PSM Signal Input Data. The Diagnostic Data
word (%AI offset 60) can contain one of the following:
PSM module firmware version
One value of the most recently captured waveform for Grid 1 or Grid 2
Diagnostic Type
Parameter 50
Value
Variable (reported in %AI offset
64)
Firmware Version
0
PSM Module Firmware Version
Grid 1 Waveform Capture address
1
Grid 1 V
A
[1]
2
Grid 1 I
A
[1]
3
Grid 1 V
B
[1]
4
Grid 1 I
B
[1]
5
Grid 1 V
C
[1]
6
Grid 1 I
C
[1]
7
Grid 1 I
N
[1]
8
Grid 1 V
A
[2]
896
Grid 1 I
N
[128]
Grid 2 Waveform Capture address
1001
Grid2 V
A
[1]
1002
Grid 2 I
A
[1]
1003
Grid 2 V
B
[1]
1004
Grid 2 I
B
[1]
1005
Grid 2 V
C
[1]
1006
Grid 2 I
C
[1]
1007
Grid 2 I
N
[1]
1008
Grid 2 V
A
[2]
1896
Grid 2 I
N
[128]