1-1-1-2-1
1
Simultaneous (Twin) -Type
1-1. Unit Specications
PZH2
2. 4-Way Cassette Type S-1014PU3E(100) ×2 / U-200PZH2E8
INDOOR MODEL S-1014PU3E(100) ×2 - -
PANEL MODEL
Standard type : CZ-KPU3 or CZ-KPU3W / ECONAVI type : CZ-KPU3A or CZ-KPU3AW
- -
OUTDOOR MODEL - U-200PZH2E8 -
Branch pipe MODEL CZ-P680BK2
Performance test condition ISO5151 / EN14511 / EN12102 / EN14825
Power supply
Ø, Hz 1Ø 50Hz 3Ø 50Hz
V 220V 230V 240V 380V 400V 415V Min Max
C
O
O
L
I
N
G
Capacity
kW 20.0 20.0 20.0 - - - 5.7 22.4
BTU/h 68200 68200 68200 - - - 19400 76400
Current A 0.82 ×2 0.79 ×2 0.76 ×2 9.10 8.65 8.35 - -
Input power
W 100 ×2 100 ×2 100 ×2 5.510k 5.510k 5.510k - -
TOTAL W - 5.710k 5.710k 5.710k 1.170k 7.100k
Annual consumption TOTAL kWh *
4
- - - - 2855 - - -
EER/EER CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 3.50 3.50 /A 3.50 4.87 3.15
ErP
*
6
Pdesign kW - - - - 20.0 - - -
η
s,c
% - - - - 326.2 - - -
Annual consumption
kWh - - - - - - - -
Class - - - - - - - -
Power factor % - - - 92 92 92 - -
Noise indoor *
7
dB-A (H/M/L) 45/38/32 - - -
Power Level dB 60/53/47 - - -
Noise outdoor
dB-A (H/L) - 59/- - -
Power Level dB - 77/- - -
H
E
A
T
I
N
G
Capacity
kW 22.4 22.4 22.4 - - - 5.0 25.0
BTU/h 76400 76400 76400 - - - 17100 85300
Current A 0.81 ×2 0.78 ×2 0.75 ×2 8.35 7.95 7.65 - -
Input power
W 95 ×2 95 ×2 95 ×2 5.070k 5.070k 5.070k - -
TOTAL W - 5.260k 5.260k 5.260k 0.960k 7.900k
COP/COP CLASS
TOTAL (W/W) *
5
/ ("A"~"G")
- - - 4.26 4.26 /A 4.26 5.21 3.16
ErP
*
6
Pdesign at -10°C kW - - - - 18.0 - - -
Tbivalent °C - - - - -10 - - -
η
s,h
% - - - - 182.2 - - -
Annual consumption
kWh - - - - - - - -
elbu(-10°C) kW - - - - 0.00 - - -
Class - - - - - - - -
Power factor % - - - 92 92 92 - -
Noise indoor *
7
dB-A (H/M/L) 45/38/32 - - -
Power Level dB 60/53/47 - - -
Noise outdoor
dB-A (H/L) - 61/- - -
Power Level dB - 79/- - -
LOW TEMP
Total capacity(kW)/Input power(W)/COP
- - - - -
EXTRA LOW TEMP
Total capacity(kW)/Input power(W)/COP
- - - -
Max Current(A) / Max Input power(W) 1.27/133 ×2 1.22/133 ×2 1.17/133 ×2 13.5 / 8.16k 13.5 / 8.59k 13.5 / 8.92k -
Starting current(A) (Cooling/Heating) - - - 9.10 / 8.35 8.65 / 7.95 8.35 / 7.65 -
Comp output(W) - 4.20k 4.20k 4.20k -
Time Delay fuse max size(A) 15 30 -
Network Impedance(ΩMAX.) - - -
Fan motor output (Indoor/Outdoor) W 90 120 × 2 -
Moisture removal volume
L/h 5.4 (2.7 ×2) - -
External static pressure Pa - - -
Indoor
Air ow *
7
Cooling m
3
/min (H/M/L) 36.0 ×2 / 26.0 ×2 / 18.0 ×2 - - -
Heating m
3
/min (H/M/L) 36.0 ×2 / 26.0 ×2 / 18.0 ×2 - - -
Outdoor Air
ow
Cooling m
3
/min - 164.0 - -
Heating m
3
/min - 164.0 - -
Refrigerant type / amount(ship) k
g
/ amount(max) k
g
- R32 4.200 7.800 -
F-Gas
GWP /
CO2eq (ton) (PRECHARGED AMOUNT) /
CO2eq (ton) (MAXIMUM CHARGED AMOUNT)
- 675 2.84 5.27
Product dimension
Height mm 319 1500 -
Width mm 840 980 -
Depth mm 840 370 -
Product dimension (Panel) H×W×D mm 33.5×950×950 - -
Packing dimension
Height mm 365 1642 -
Width mm 898 1095 -
Depth mm 898 529 -
Weight
(NET) k
g
25 117 -
(GROSS)
k
g
31 129 -
Panel (NET)
k
g
5 - -
Layers limit (actually) 11 (12) 1 (2) -
Operation condition
Cool (DBT) 18°C ~ 32°C -15°C ~ 46°C -
Heat (DBT) 16°C ~ 30°C -20°C ~ 24°C -
Max Working Pressure HP/LP MPa 4.15/2.70 -
P
I
P
I
N
G
Pipe port diameter mm (inch) (Liquid)Ø9.52(3/8) (Gas)Ø15.88(5/8) (Liquid)Ø9.52(3/8) (Gas)Ø25.4(1) -
Pipe diameter mm (inch) (Liquid)Ø9.52(3/8) (Gas)Ø25.4(1) -
Connecting method ared type (Liquid)ared type (Gas)brazing connection -
Standard length m 7.5 m -
Pipe length range m
5 ~ 80 m -
Indoor unit & Outdoor unit height dierence m
30 m(OD located lower) / 30 m(OD located higher) -
Add gas amount
g
/m 60
g
/m
Pipe length for additional gas m 30m -
* In the case of nanoe X OFF
*1 In case it is necessary to indicate the air ow volume in (l/s), the value in (m³/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
If the EUROVENT Certied models can be operated under the "extra-low" temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage 230V shall be used.
*3 Network Impedance shall be applicable for EUROPE and CHINA models.
*4 The annual consumption is calculated by multiplying the input power at 230V(400V) by an average of 500 hours per year in cooling mode.
*5 EER and COP classication is at 230V(400V) only in accordance with EU directive 2002/31/EC.
*6 η
s,c
and η
s,h
classication is at 230V(400V) only in accordance with EN-14825. For heating, η
s,h
indicates the value of only Average heating season.
*7 H:High at setting 5 stage (Level 5), M:Middle at setting 5 stage (Level 3), L:Low at setting 5 stage (Level 1)
SM830281-00_欧州向け R32シングル TD&SM.indb 1 20/01/09 14:59:17