6-11
66
Never use the DN code unlisted in the following table. (P) : Factory preset mode
DN Item Setting No.
05 Outdoor fan silent mode
1=Silent mode 1 (P)
2=Silent mode 2,,,,, 3=Silent mode 3
07 Capacity matching ignored 0=Invalid (P) 1=Valid
0C Indoor unit drain pump forced operation
0=Invalid
1=stop for 2 hours and drive for 20 minutes constantly
2=stop for 20 minutes and drive for 20 minutes constantly
3=Drive constantly
4-6=delay drive when thermostat OFF
7=delay drive when thermostat OFF (P)
0D
Measures against smell when indoor unit cooling
thermostat OFF
0=Invalid (P)
1=Measures against smell
1A Demand 1 current (%)
0=0% 40=40%
45=45%,,,,, 75=75% (P) ,,,,,
130=130% -1=No control
1B Demand 2 current (%)
0=0% 40=40%
45=45%,,,,, 50=50% (P) ,,,,,
130=130% -1=No control
1D Current control level
0=40%
1=45%,,,,, 12=100%,,,,, 16=120%,,,,,
18=130,,,,, 19=-1(Invalid)(P)
2B DP operation time for slime measures
20=20 minutes 30=30 minutes (P)
40=40 minutes 50=50 minutes
60=60 minutes
80 Refrigerant Type 410=R410A(P), 22=R22, 407=R407C, 32=R32
81
Outdoor unit capacity
(Setting when the data is not stored in the EEPROM.
Do not change under normal conditions.)
0=Invalid 224 (Type 200) 280 (Type 250)
SM830281-00_欧州向け R32シングル TD&SM.indb 11 19/11/08 11:43:47