FP2/FP2SH Program Conversion Function
4-4
High-level instructions
FP2/FP2SH instruction
FP7 instruction
High-level
instruction
(Boolean)
Operand condition
Boolean
Name
Operation
unit
Bit manipulation instructions
F130(BTS)
When specifying a 16-bit device only
(WX/WY/WR/WL/DT/LD)
BTS
Bit set
US
When specifying SV/EV/IX device for
operand
Cannot be converted.
F131(BTR)
When specifying a 16-bit device only
(WX/WY/WR/WL/DT/LD)
BTR
Bit reset
US
When specifying SV/EV/IX device for
operand
Cannot be converted.
F132(BTI)
(*) When specifying a 16-bit device
only
(WX/WY/WR/WL/DT/LD)
BTI
Bit Inversion
US
When specifying SV/EV/IX device for
operand
Cannot be converted.
F133(BTT)
(*) When specifying a 16-bit device
only
(WX/WY/WR/WL/DT/LD)
BTT
Bit Test
US
When specifying SV/EV/IX device for
operand
Cannot be converted.
* : There is no change from the versions before Ver.2.10 of FPWIN GR7(S).

Other manuals for Panasonic FP7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP7 Series and is the answer not in the manual?

Panasonic FP7 Series Specifications

General IconGeneral
BrandPanasonic
ModelFP7 Series
CategoryController
LanguageEnglish

Related product manuals