1-10-17
11
 Wiring samples
Type U2
Use this screw when connecting the shield  
for the Inter-unit control wiring to ground.
(
 : Functional earthing)
*1 Fasten tightly.
Earth Wiring:
Make the earth wiring 25 - 30 mm longer than power 
cable.
Power Supply
Power cable
Inter-unit Control 
Wiring
Clamper
*
1
(supplied)
Clamper
*
1
(supplied)
Clamping
Clip
Remote Control 
Wiring
Insulation tape
8 mm
Insulation tape
Shield mesh
Shield mesh
Fig. 1-10-8
Fig. 1-10-9
Fig. 1-10-10
Fig. 1-10-11
 Examples of shield wires
(1)  Remove cable coat not to scratch braided shield. (Fig. 1-10-8) 
(2)  Unbraid the braided shield carefully and twist the 
unbraided shield wires tightly together. Insulate the shield 
wires by covering them with an insulation tube or wrapping 
insulation tape around them. (Fig. 1-10-9)
(3)  Remove coat of signal wire. (Fig. 1-10-10)
(4)  Attach ring pressure terminals to the signal wires and the 
shield wires insulated in Step (2). (Fig. 1-10-11)
Stranded wire
Ring 
pressure 
terminal
Screw and 
Special washer
Ring 
pressure 
terminal
Terminal board
Ring pressure 
terminal
Screw
Special 
washer
Wire
Wire
Strip 10 mm
Fig. 1-10-6
Fig. 1-10-7
How to connect wiring to the terminal
 For stranded wiring
(1)
then strip the insulation to expose 
the stranded wiring about 10 mm and 
tightly twist the wire ends. (Fig. 1-10-6)
(2)
remove the terminal screw(s) on the 
terminal board.
(3)
pliers, securely clamp each stripped 
wire end with a ring pressure terminal.
(4)
Cut the wire end with cutting pliers, 
Using a Phillips head screwdriver, 
Using a ring connector fastener or 
Place the ring pressure terminal, 
and replace and tighten the removed 
terminal screw using a screwdriver. 
(Fig. 1-10-7)
SM830266-00_大洋州向けR32シングルTD&SM.indb   17 18/03/29   10:20:01