SELECTING THE INSTALLATION SITE
Outdoor Unit
AVOID:
heat sources and exhaust fans, etc.
damp, humid or uneven locations.
do not install at a location that can become a habitat for small animals or depositing
fallen leaves.
DO:
choose a place as cool as possible.
choose a place that is well ventilated and outside air temperature does not
exceed maximum 46°C constantly.
allow enough room around the unit for air intake/exhaust and possible maintenance.
use lug bolts or equal to bolt down unit, reducing vibration and noise.
If cooling operation is to be used when the outdoor air temperature is –5°C or below, install a duct and chamber on the outdoor unit.
Installation space for outdoor unit
Install the outdoor unit with a sufficient space around the outdoor unit for operation and maintenance.
(A) When an obstruction is present on the air inlet side
When the upward area is open
(1) One outdoor unit installed individually
Obstruction only on air inlet side
Obstruction on both sides
a
a 50 mm or more
a
c
b
a 50 mm or more
b 50 mm or more
c 250 mm or more
(2) Two or more outdoor units installed side by side
Obstructions on both sides
a
b
c
d
a 200 mm or more
b 150 mm or more
c 250 mm or more
d 250 mm or more
When an obstruction is present also in the upward area (Do not use the air-discharge chamber.)
(1) One outdoor unit installed individually
Obstruction only on air inlet side
Obstruction also on the air inlet side and both sides
a
b
c
a 50 mm or more
b 500 mm or less
c 300 mm or more
a
b
c
e
d
a 50 mm or more
b 50 mm or more
c 250 mm or more
d 500 mm or less
e 1,000 mm or more
(2) Two or more outdoor units installed side by side
Obstruction also on the air inlet side and both sides
a
b
c
d
f
e
a 400 mm or more
b 1,000 mm or more
c 250 mm or more
d 250 mm or more
e 500 mm or less
f 1,000 mm or more
Exhaust fan
Heat source
Outdoor unit
Hot air
SM830266-00_大洋州向けR32シングルTD&SM.indb 1 18/03/29 10:20:02