1
1-11-102
Type G H J K
60, 71
900
(Pitch 150 × 6)
25 13 18
100, 125, 140
1,350
(Pitch 150 × 9)
0 13 24
Connecting Duct to Air Intake Port Side
(1) First pull out a filter in the direction of the electrical
equipment box in the unit.
The pre-installed filter will not be used any more.
Pull out
Bracket
Packing
Filter
(2) Then remove the seal packing, bracket and filter attached
to the side of the air intake port.
(3) Install the duct (field supply).
See the figure for the dimension of the installation hole.
Use M5 self-tapping screws for installation.
K - ø4.1 hole
For M5 self-tapping
screw
250
150
HGH
50 50
J
NOTE
Select an air-intake grille with a filter at a local shop.
To get clean air and to extend the service life of the air
conditioner, an air filter must be installed in the air intake.
For installation and cleaning the air filter, consult your dealer
or service center.
Unit: mm
SM830266-00_大洋州向けR32シングルTD&SM.indb 102 18/03/29 10:21:15