SELECTING THE LOCATION FOR THE INDOOR UNIT
Required Minimum Space for Installation and Service.
Provide a check port on the piping side ceiling for repair and maintenance.
Install the indoor unit once the following conditions are satisfi ed and after receiving the customer approval.
1. The indoor unit must be within a maintenance space.
2. The indoor unit must be free from any obstacles in path of the air inlet and outlet, and must allow spreading of air
throughout the room.
Top view
(Unit:mm)
Inspection hole
Control box
(600 x 600)
600
<Front>
1000
600
Front view
Ha
Above 250cm
(Recommended)
TYPE Ha
S-60PE1R5B 290
S-71PE1R5B 360
S-100PE1R5B 360
S-125PE1R5B 430
S-145PE1R5B 430
* The Ha is necessary for the access to the
top of the unit for repair.
* If the height from the floor to ceiling exceeds three meters, air flow distribution deteriorates and the effect is
decreased.
INSTALLATION OF INDOOR UNIT
Fig. 1-11-19
POSITION OF SUSPENSION BOLT
540
700
1160
1100
1~3mm
Drainage hole
Apply a joint-canvas between the unit and duct to
absorb unnecessary vibration.
Install the unit leaning to a drainage hole side as a
gure for easy water drainage.
Fig. 1-11-20
H
F
E E
F F
F
G
79
81
TYPE E F G H
S-60PE1R5B 130 33.1 290 118
S-71PE1R5B
S-100PE1R5B
195 35.7 360 50
S-125PE1R5B
S-140PE1R5B
260 38.2 430 121.5
Fig. 1-11-21
(unit: mm)