REFERENCE & INSTALLATION MANUAL
8.3 TAMPER RECOGNITION
Section [132]: Zone Options
[1] OFF / [2] OFF: Tamper Recognition Disabled (default)
If the system is armed or disarmed
, the control panel will display the zone as open in the keypad display, but will not generate
an alarm. This option is not permitted on UL systems.
[1] OFF / [2] ON: Trouble Only
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20).
If the system is disarmed
and a tamper wiring failure occurs on a zone, a Tamper/Zone Wiring Failure will appear
in the keypads’ Trouble Display (see page 47) and the control panel will transmit the appropriate Zone Tamper report code (see
page 34).
[1] ON / [2] OFF: Silent Alarm
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20). In a disarmed system, it functions the same as the Trouble Only setting, but it will also generate a silent alarm. A
silent alarm will not trigger any bells or sirens, but the system will have to be disarmed.
[1] ON / [2] ON: Audible Alarm
In an armed system and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20). In a disarmed system, it functions the same as Trouble Only setting, except it will also generate an audible
alarm.
8.3.1 TAMPER BYPASS OPTIONS
Section [132]: Zone Options
Option
[3]
OFF = Will generate a tamper if de tected on a bypass ed zo ne (default)
Option
[3]
ON = Tampers on bypassed zones will be ignored
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the control panel
will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper Recognition ignores the bypass
definition. This means the control panel will generate an incident as per Tamper Recognition settings if a tamper or
wire fault occurs on a bypassed zone.
8.4 KEYPAD PANIC OPTION S
Section [128]: General Options
Option
[1]
OFF = Emergency Panic Disabled (default)
Option
[1]
ON = Emergency Panic Enabled
Pressing the [1] and [3] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [4].
Option
[2]
OFF = Auxiliary Panic Disabled (default)
Option
[2]
ON = Au xili ary Pani c En ab led
Pressing the [4] and [6] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [5].
Option
[3]
OFF =
Fire Panic Disabled (default)
Option
[3]
ON =
Fire Panic Enabled
Pressing the [7] and [9] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [6].
Option
[4]
OFF = Emergency Panic is Silent (default)
Option
[4]
ON = Emergency Panic is Audible
Option
[5]
OFF = Auxili ary Pani c is Sile nt (defa ul t)
Option
[5]
ON = Auxili ary Pani c is Aud ibl e
Option
[6]
OFF = Fire Panic is Silent (default)
Option
[6]
ON =
Fire Panic is Pulsed
Silent alarm
:
The control panel emits a Confirmation Beep and transmits the appropriate Panic report code if programmed in section [195]. The
control panel will not enable the keypad buzzers or the control panel’s
BELL output (no audible alarm).
Audible alarm
:
Same as silent alarm, except the keypad buzzers and the
BELL output will activate until a user cancels the alarm (disarms) with a
valid User Access Code or when the Bell Cut-Off Timer elapses (see page 29).
Fire (pulsed) alarm
:
Same as audible operation, except that the
BELL output will be pulsed as shown in Figure on page 20.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Paradox Spectra 1759EX V1.0 and is the answer not in the manual?

Paradox Spectra 1759EX V1.0 Specifications

General IconGeneral
BrandParadox
ModelSpectra 1759EX V1.0
CategoryControl Unit
LanguageEnglish

Related product manuals