8.3 TAMPER RECOGNITION
Section [132]: Zone Options
[1] OFF / [2] OFF: Tamper Recognition Disabled (default)
If the system is armed or disarmed
, the control panel will display the zone as open in the keypad display, but will not generate
an alarm. This option is not permitted on UL systems.
[1] OFF / [2] ON: Trouble Only
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20).
If the system is disarmed
and a tamper wiring failure occurs on a zone, a Tamper/Zone Wiring Failure will appear
in the keypads’ Trouble Display (see page 47) and the control panel will transmit the appropriate Zone Tamper report code (see
page 34).
[1] ON / [2] OFF: Silent Alarm
If the system is armed
and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20). In a disarmed system, it functions the same as the Trouble Only setting, but it will also generate a silent alarm. A
silent alarm will not trigger any bells or sirens, but the system will have to be disarmed.
[1] ON / [2] ON: Audible Alarm
In an armed system and a tamper wiring failure occurs on a zone, the control panel will follow the zone's Alarm Types setting
(see page 20). In a disarmed system, it functions the same as Trouble Only setting, except it will also generate an audible
alarm.
8.3.1 TAMPER BYPASS OPTIONS
Section [132]: Zone Options
Option
[3]
OFF = Will generate a tamper if de tected on a bypass ed zo ne (default)
Option
[3]
ON = Tampers on bypassed zones will be ignored
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the control panel
will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper Recognition ignores the bypass
definition. This means the control panel will generate an incident as per Tamper Recognition settings if a tamper or
wire fault occurs on a bypassed zone.
8.4 KEYPAD PANIC OPTION S
Section [128]: General Options
Option
[1]
OFF = Emergency Panic Disabled (default)
Option
[1]
ON = Emergency Panic Enabled
Pressing the [1] and [3] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [4].
Option
[2]
OFF = Auxiliary Panic Disabled (default)
Option
[2]
ON = Au xili ary Pani c En ab led
Pressing the [4] and [6] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [5].
Option
[3]
OFF =
Fire Panic Disabled (default)
Option
[3]
ON =
Fire Panic Enabled
Pressing the [7] and [9] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [6].
Option
[4]
OFF = Emergency Panic is Silent (default)
Option
[4]
ON = Emergency Panic is Audible
Option
[5]
OFF = Auxili ary Pani c is Sile nt (defa ul t)
Option
[5]
ON = Auxili ary Pani c is Aud ibl e
Option
[6]
OFF = Fire Panic is Silent (default)
Option
[6]
ON =
Fire Panic is Pulsed
Silent alarm
:
The control panel emits a Confirmation Beep and transmits the appropriate Panic report code if programmed in section [195]. The
control panel will not enable the keypad buzzers or the control panel’s
BELL output (no audible alarm).
Audible alarm
:
Same as silent alarm, except the keypad buzzers and the
BELL output will activate until a user cancels the alarm (disarms) with a
valid User Access Code or when the Bell Cut-Off Timer elapses (see page 29).
Fire (pulsed) alarm
:
Same as audible operation, except that the
BELL output will be pulsed as shown in Figure on page 20.