6-20 Programming Your Application
650V AC Drive
400V Build Power Dependent Defaults
Frame 3
Parameter Function Block Tag
POWER MOTOR DATA 1158
3.00 kw 4.00 kw 5.50 kw 7.50 kw
MOTOR CURRENT MOTOR DATA 64
6.80 A 9.00 A 12.00 A 16.00 A
MAG CURRENT MOTOR DATA 65
2.36 A 3.36 A 3.39 A 4.38 A
NAMEPLATE RPM MOTOR DATA 83
1420.0 RPM 1420.0 RPM 1445.0 RPM 1450.0 RPM
MOTOR VOLTAGE MOTOR DATA 1160
400.0 V 400.0 V 400.0 V 400.0 V
POWER FACTOR MOTOR DATA 242
0.8 0.8 0.8 0.8
STATOR RES MOTOR DATA 119
2.0620 ohms 2.0620 ohms 1.3625 ohms 1.0545 ohms
LEAKAGE INDUC MOTOR DATA 120
43.76 mH 43.76 mH 43.37 mH 33.57 mH
MUTUAL INDUC MOTOR DATA 121
175.03 mH 175.03 mH 173.48 mH 134.27 mH
ROTOR TIME CONST MOTOR DATA 1163
136.75 ms 136.75 ms 276.04 ms 303.65 ms
BRAKE POWER DYNAMIC BRAKING 78
0.2 kW 0.2 kW 0.5 kW 0.5 kW
FREQUENCY INJ BRAKING 577
9.0 Hz 9.0 Hz 9.0 Hz 9.0 Hz
DEFLUX TIME INJ BRAKING 710
0.5 s 0.5 s 0.5 s 0.5 s
BASE VOLTS INJ BRAKING 739
100.00 % 100.00 % 100.00 % 100.00 %
DC LEVEL INJ BRAKING 581
3.0 % 3.0 % 3.0 % 3.0 %
DC PULSE INJ BRAKING 579
2.0 s 2.0 s 2.0 s 2.0 s
FINAL DC PULSE INJ BRAKING 580
1.0 s 1.0 s 1.0 s 1.0 s
FIXED BOOST FLUXING 107
5.00% 5.00% 5.00% 5.00%
ACCEL TIME REFERENCE RAMP 258
10.0 s 10.0 s 10.0 s 10.0 s
DECEL TIME REFERENCE RAMP 259
10.0 s 10.0 s 10.0 s 10.0 s
DEFLUX DELAY PATTERN GEN 100
2.0 s 2.0 s 2.0 s 2.0 s
SEARCH VOLTS FLYCATCHING 573
9.00 % 9.00 % 9.00 % 9.00 %
SEARCH BOOST FLYCATCHING 32
40.00 % 40.00 % 40.00 % 40.00 %
SEARCH TIME FLYCATCHING 574
5.0 s 5.0 s 5.0 s 5.0 s
REFLUX TIME FLYCATCHING 709
3.0 s 3.0 s 3.0 s 3.0 s
OVERLOAD MOTOR DATA 1164
2.0 2.0 2.0 2.0
SPEED PROP GAIN SPEED LOOP 1187
20 20 20 20
SPEED INT TIME SPEED LOOP 1188
500. ms 500. ms 500. ms 500. ms
MOTOR CONNECTION MOTOR DATA 124
1 : STAR 1 : STAR 1 : STAR 1 : STAR
BRAKE RESISTANCE DYNAMIC BRAKING 77
100 100 56 56
BOOST MODE FLUXING 1058
1 1 1 1
Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN +46 (0)18-65 70 00 +46 (0)18-10 74 78 info@regal.se www.regal.se