Loading...
Applications 12-5
650V AC Drive
Application 2: Auto/Manual Control
Two Run inputs and two Setpoint inputs are provided. The Auto/Manual switch selects which pair of inputs is active.
The Application is sometimes referred to as Local/Remote.
Manual
User Relay
10
9
8
7
6
5
4
3
2
1
RL1A
RL1B
13
12
11
WIRE
SINGLE
STARTING
DIN7
(ENCB)
DIN6
(ENCA)
DIN5
DIN4
DIN3
SELECT
24V = run forward
REMOTE REVERSE
0 V = remote forward, 24V = remote reverse
DIN2
DIN1
24V = run forward
+24V
DOUT3 (relay)
0V
not used
Control
Terminal
COAST STOP
24V = coast to stop, 0 V = drive may run
AUTO RUN
24V = run forward
Setpoint
Auto
Setpoint
DEMAND (0 V = 0%, 10V = 100%)
4 mA = 0%, 20mA = 100%
0V = 0%, 10V = 100%
RELAY SOURCE
HEALTH i.e. 0 V = not healthy
= 0
= 3
= 1
= 1
default source
A or V
= 4
-
20m
A
AOUT1
AOUT2
AIN2
AIN1
0V
MANUAL RUN
+24V
RAMP OUTPUT
+10V REF
AUTO SETPOINT
MANUAL SETPOINT
not used