Applications 12-7
650V AC Drive
Application 3: Preset Speeds
This is ideal for applications requiring multiple discrete speed levels.
The setpoint is selected from either the sum of the analogue inputs, (as in Application 1 and known here as PRESET 0), or
as one of up to seven other pre-defined speed levels. These are selected using DIN2, DIN3 and DIN4, refer to the Truth
Table below.
Edit parameters AP2 to AP8 on the keypad to re-define the speed levels of PRESET 1 to PRESET 7. Reverse direction is
achieved by entering a negative speed setpoint.
Preset Speed Truth Table
DIN4 DIN3 DIN2 Preset
0V 0V 0V 0
0V 0V 24V 1
0V 24V 0V 2
0V 24V 24V 3
24V 0V 0V 4
24V 0V 24V 5
24V 24V 0V 6
24V 24V 24V 7
Lefflersgatan 1, SE-754 50 Uppsala, SWEDEN +46 (0)18-65 70 00 +46 (0)18-10 74 78 info@regal.se www.regal.se