Running in Local
On the 890CD keypad select LOCAL mode. The display will show the Local Setpoint : 0.0%
Use the UP arrow to set a Local Setpoint, say 20%.
Press the green RUN button. The motor will accelerate to the desired speed and maintain it. Adjust
RAMP ACCEL TIME (S3) in Quick Setup to the desired level.
Press the red STOP button. The motor will decelerate to a stop. Adjust RAMP DECEL TIME (S4) in
Quick Setup to desired level. If the drive trips on Overvoltage, extend the RAMP DECEL TIME or
connect a braking resistor. Refer to the 890 Engineering Reference Manual.
Go to SYS::SAVE::APP and UP arrow to save your settings Values are stored during power-down.
Running in Remote
On the 890CD keypad select REMOTE mode. The display will show the remote Setpoint : ?.?%
(The value displayed depends on the external speed reference).
Dial in a speed setpoint using the Speed potentiometer until the display reads 20%.
Start the drive by closing the Start contact between terminal X14/03 and terminal X15/02. The
motor will accelerate to the desired speed and maintain it. Adjust RAMP ACCEL TIME (S4) in Quick
Setup to the desired level.
Open the Start contact. The motor will decelerate to a stop. Adjust RAMP DECEL TIME (S4) in
Quick Setup to desired level. If the drive trips on Overvoltage, extend the RAMP DECEL TIME or
connect a braking resistor. Refer to the 890 Engineering Reference Manual.
Go to SYS::SAVE::APP and UP arrow to save your settings Values are stored during power-down.