Page 19
Running in Local
• On the 890CD keypad select LOCAL mode. The display will show the Local Setpoint : 0.0%
• Use the UP arrow to set a Local Setpoint, say 20%.
• Press the green RUN button. The motor will accelerate to the desired speed and maintain it. Adjust
RAMP ACCEL TIME (S3) in Quick Setup to the desired level.
• Press the red STOP button. The motor will decelerate to a stop. Adjust RAMP DECEL TIME (S4) in
Quick Setup to desired level. If the drive trips on Overvoltage, extend the RAMP DECEL TIME or
connect a braking resistor. Refer to the 890 Engineering Reference Manual.
Go to SYS::SAVE::APP and UP arrow to save your settings Values are stored during power-down.
Running in Remote
• On the 890CD keypad select REMOTE mode. The display will show the remote Setpoint : ?.?%
(The value displayed depends on the external speed reference).
• Dial in a speed setpoint using the Speed potentiometer until the display reads 20%.
• Start the drive by closing the Start contact between terminal X14/03 and terminal X15/02. The
motor will accelerate to the desired speed and maintain it. Adjust RAMP ACCEL TIME (S4) in Quick
Setup to the desired level.
• Open the Start contact. The motor will decelerate to a stop. Adjust RAMP DECEL TIME (S4) in
Quick Setup to desired level. If the drive trips on Overvoltage, extend the RAMP DECEL TIME or
connect a braking resistor. Refer to the 890 Engineering Reference Manual.
Go to SYS::SAVE::APP and UP arrow to save your settings Values are stored during power-down.