5.4 Confi guration condensate drain
There are three modes of operation:
CAPACITIVE = Automatic drainign using a capacitive sensor;
TIMED = programmable draining times;
CONTINUOUS (external) = if there is an external drain.
1. Press
set
and
esc
together at the same time to enter general menu “PAr” .
2. Press
set
to enter.
3. Use the arrows
or to fi nd menu “ Cd“.
4. Press
set
to enter.
5. Use the arrows
or to fi nd parameter “ d3“.
6. Press
set
to choose the type of the drain:
0 = external;
1 = timed;
2 = capacitive.
7. Press
set
for fi ve seconds to select the drain.
CF9
set
Y
d1
esc
Y
Y
........
Y
Cd
d3
Y
Y
d2
Y
Y
set
Y
0
esc
Y
Y
Y
1
Y
Y
2
PAr
esc
set
Y
Y
set
esc
Y
Y
For the option (1) timed drain,it is possible to set the ON/OFF time of the drain. On menu “ Cd
1. Use the arrows
or to fi nd the parameter d1” to set the opening time.
2. Press
set
to confi rm.
3. Use the arrows or to fi nd the parameter d2 ” to set the closing time.
4. Press
set
to confi rm.
5. Press
esc
to exit.
5.5 Visualization of temperature probes
On display appear the dew point temperature as defoult.
To view other temperatures, proceed as follows:
1. Use the arrows
or chosse the sensor.
b0 = dew point temperature sensor;
b2= evaporation temperature sensor;
b5= Suction compressor temperature sensor;
b8 = condensation temperature sensor;
P1 = High pressure sensor
Once chosen wait a few seconds and the probe value will appear.
2. Press
esc
to exit.
...
b0
Y
b2
Y
Y
....
0.0
If you switch OFF the dryer with
set
, when you switch ON the sensor you chose remains memorized.
If you switch OFF the dryer with the MAIN SWITCH “
&
, when you switch ON returns to reading
the B0 sensor.