7/20
PSE 120-350
5.6 Modbus ON/OFF
1. Press
set
and
esc
together at the same time to enter general menu “PAr” .
2. Press
set
to enter on menu “ CF9“.
3. Use the arrows
or to fi nd parameter “ A5, “CF30”,CF31”,CF32”.
4. Press
set
to enter.
PARAMETER CODE TYPE DEFAULT
Modbus on / off enabling
A5
D
OFF
Unit address
CF30
D
1
Baud rate
CF31
D
5
Parity
CF32
D
1
Modbus enabling
Enables the modbus function.
Unit address
Give an address to your unit.
Baud rate
1
2400
3
9600
5
38400
7
115200
2
4800
4
19200
6
57600
Parity : 1 = EVEN; 2 = NONE; 3 = ODD
5.7 ON/OFF remoto
1. Press
set
and
esc
together at the same time to enter general menu “PAr”.
2. Press
set
to enter on menu “ CF9“.
3. Use the arrows
or to fi nd parameter “ A7 “.
4. Press
set
to enter.
5. Use the arrows
or to choose:
ON : remote ON;
OFF: remote OFF.
6. Press
set
to confi rm.
7. Press
esc
to exit.
Y
Y
Y
esc
set
Y
set
Y
CF9
esc
Y
set
Y
C_F
esc
Y
PAr
OFF
Y
A7
0n
set
Y
esc
Y
Y
Y To manage REMOTE OFF mode, remove the bridge between terminals: 87 -GND and connect the
remote start/stop switch (to be provided for by the customer).
Y
Y
Y
esc
set
Y
set
Y
CF9
esc
Y
set
Y
A1
esc
Y
PAr
OFF
Y
A5
0n
set
esc
Y
Y
Y
CF30 CF31
CF32