5.8 CYCLING function
1. Press 
set
 and  
esc
 together at the same time to enter general menu “PAr” .
2. Press 
set
  to enter on menu .
3.  Use the arrows  
 or   to fi nd parameter “ C4C“.
4. Press 
set
  to enter on menu .
5.  Use the arrows  
 or   to fi nd parameter “ C7“. 
6. Press 
set
 to choose:
ON : continuous;
OFF: cycling.
7. Press 
set
 to confi rm.
8. Press 
esc
 to exit.
esc
 
set
set
CF9
esc
set
On
esc
PAr
OFF
C4C
C7
set
esc
C37
“C37” show the % of energy saving.
5.9 Alarm management
1. Press 
set
 and  
esc
 together at the same time to enter general menu “PAr” .
2. Press 
set
  to enter on menu “ CF9“.
3.  Use the arrows  
 or   to fi nd parameter  “ CFJ1 “.
PARAMETER CODE TYPE DEFAULT
Alarm relay management 
CFJ1
D
OFF
OFF = alarm; On = warning /alarm
In an alarm/warning situation, follow the procedure below:
1. Press 
set
  to enter menu of direct parameters.
2.  Use the arrows  
 or   to fi nd parameter “ AL“.
3. Press 
set
  to see alarm code:
set
HiSt
set
Hd
esc
AL
.....
ALARM LIST  WARNING LIST
H.C. Cod. Description Reset H.C. Cod. Description Reset
10 LD Low dew point M 1/2 FBO/2 B0/2 sensor warning A
11 LT Low evaporation temperature M 3/5 FB5/8 B5/8 sensor warning A
13 HT2 High discharge temperature M 7 FP1 PI sensor warning A
18 HP High pressure M 24 DRE Condensate drain warning A
19 LP Low Pressure M 9HDHigh dew point warning A
21 PI Compressor Thermal protect. M 12 HT1 High discharge temp. A
22 PH Inverted phases M 14 HB5 High suction compres. temp. A
20 HP1 High pressure  A
 
(H.C=History code) 25 SR Maintenance A