EasyManuals Logo

Parker Sporlan Subcool Control User Manual

Parker Sporlan Subcool Control
24 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Bulletin 100-50-5.2 – Page 13
APPENDIX F - Parameter Definitions
DISPLAY MEANING DESCRIPTION
ESC
Escape
Escape from the Settings Menu and Return to Process
Variables Menu
LoSP
Liquid Outlet Temperature Control Setpoint
The target control temperature of the liquid leaving the
heat exchanger
rghL
Return Gas High Limit
Limits the temperature of the superheated refrigerant to a
maximum target value (Limits superheat PID target)
SboF
Subcooler Off Temperature Differential
Temperature differential above the liquid outlet tempera-
ture setpoint that the liquid inlet temperature must fall
below in order to switch to OFF mode. Will switch back to
cooling after the liquid inlet temperature rises above the
liquid outlet temperature + subcooler off temperature
differential + 5 degrees F
SHSP
Superheat Setpoint
The minimum target superheat setpoint that the superheat
PID can try to maintain
rEFr
Refrigerant
The currently selected refrigerant used to calculate the
saturation temperature based on suction pressure
HiCP
Maximum Stepper % Open The maximum % open of the valve referenced to full stroke
-LP-
Liquid Proportional Gain Coefcient Liquid Proportional Gain Coefcient
-L-
Liquid Integral Gain Coefcient Liquid Integral Gain Coefcient
-Ld-
Liquid Derivative Gain Coefcient Liquid Derivative Gain Coefcient
-SP-
Superheat Proportional Gain Coefcient Superheat Proportional Gain Coefcient
-S-
Superheat Integral Gain Coefcient Superheat Integral Gain Coefcient
-Sd-
Superheat Derivative Gain Coefcient Superheat Derivative Gain Coefcient
LSHi
Low Superheat Integral Gain Coefcient
The integral gain coefcient to use for the superheat PID
loop if the superheat is below 3 degrees F
CyCt
Cycle Time The PID update time
StEP
Stepper Type
The number of steps of resolution for the stepper valve at
full stroke
SPoS
Manual Stepper Position
Overrides the stepper valve position and moves to the
desired percent open relative to full stroke of the valve
Addr
Network Address The address of the controller on the MODBUS network
bAvd
Network Baud Rate
The baud rate in hundreds of bits per second of the MOD-
BUS network
nPAr
Network Parity Mode The network parity mode of the MODBUS network
nP
Units of Pressure
The units of pressure the controller uses to display (PSI or
Bar)
nt
Units of Temperature
The units of temperature the controller uses to display
(Fahrenheit or Celsius)
tt4P
Temperature Sensor Type
The type of thermistor connected to the controller (2K type
or 3K type)
Pt4P
Pressure Sensor Type
The type of pressure sensor connected to the controller
(absolute or gauge type)
Prng
Pressure Sensor Range
The range of the pressure sensor connected to the control-
ler (0-150 PSI, 0-300 PSI, or 0-500 PSI)
CALP
Pressure Calibration Offset Adds a constant offset to the pressure reading
CLt1
T1 Temperature Calibration Offset Adds a constant offset to the T1 temperature reading
CLt
T2 Temperature Calibration Offset Adds a constant offset to the T2 temperature reading
CLt3
T3 Temperature Calibration Offset Adds a constant offset to the T3 temperature reading
CLt4
T4 Temperature Calibration Offset Adds a constant offset to the T4 temperature reading
Cadr
Controller Address on Display Network
Controller must be set to 0 (Standalone) No display net-
working option

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Sporlan Subcool Control and is the answer not in the manual?

Parker Sporlan Subcool Control Specifications

General IconGeneral
BrandParker
ModelSporlan Subcool Control
CategoryController
LanguageEnglish

Related product manuals