green LED is blinking, pressing PB2 will decrement the set point
by 1°F. Do not press any pushbutton for 5 to 10 seconds or until the
green LED stops blinking. The controller will use the last display
for the leaving liquid temperature set point and will go back to
normal operation.
REMOTE PANEL DISPLAY
A remote panel display is available that will allow access to all the param-
eters that the controller uses. The Remote Panel Display can be used as a
set point tool in production, a diagnostic tool in the field or as a permanent
readout device on the controller. A five foot cable is included.
Plugtheremotedisplayintothetelephonejack(J9)onthecontroller.The
following is a list of readings available:
POSN Number of steps the electric expansion valve is open
SUPH Superheat read by controller
LQTP Temperature read by the leaving liquid temperature sensor (-50
to 102°F.)
PRES Pressure read by the transducer (0-153 psi absolute or gauge)
TOUT Temperature read by the suction temperature sensor
(-50 to 102°F.)
TSAT Saturated Temp. Based on suction pressure and refrigerant
selected
COOL, PMDN
COOLwheninnormaloperation,PMDNwheninpumpdown
R22, 404A, R422, R507
R22 for refrigerant R22, 404A for refrigerant R404A, R422 for
refrigerant R422D, and R507 for refrigerant R507.
LARG, SMAL, MEDM
LARG if the EEV used is an SEI-50 or larger. SMAL if the
EEV used is smaller than an SEI-30. MEDM if the EEV used is
a SEI-30.
SHSP Superheat set point (5 to 30°F.)
LQSP LeavingliquidTemperaturesetpoint(-40to100°F)
GAIN Proportional gain set point. Number of steps per degree that
liquid temperature is above or below its set point (0 to 255 steps
perdegree).Defaultis44forLARGsetting,22forMEDMset-
ting,and10forSMALsetting.
INTG Integral set point. Number of seconds the controller waits to
update the reference valve position. (1 to 120 seconds). Default
is 50 seconds.
DERI Derivative set point. Number of steps the controller opens or
closes the valve based on the rate the leaving liquid temperature
is changing (0 to 255 seconds). Default is 20.
Pressing ENTER will toggle display between one of the displays
described above and the numeric value read for that particular display.
Pressing UP will scroll through the menu from POSN to SUPH, etc.
Pressing DOWN will scroll through the menu the opposite way.
POSN MODE
Press and hold UP button and ENTER button for 5 seconds to put the
valve in manual valve position. The number of steps open will be dis-
playedandthe1000’sdigitwillblink.
Pressing the UP button will open the valve 1000 steps.
Pressing the DOWN button will close the valve 1000 steps.
Pressing the ENTER button will change the flashing digit from 1000’s
digittothe100’sdigit.
Pressing the UP button will open the valve 100 steps.
Pressing the DOWN button will close the valve 100 steps.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom100’sdigit
tothe10’sdigit.
Pressing the UP button will open the valve 10 steps.
Pressing the DOWN button will close the valve 10 steps.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom10’sdigit
tothe1’sdigit.
Pressing the UP button will open the valve 1 step.
Pressing the DOWN button will close the valve 1 step.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom1’sdigit
tothe1000’sdigit.
Press and hold UP button and ENTER button for 5 seconds will put the
controllerinnormalcontrol.Thedigitswillstopblinking.
SHSP MODE
Press and hold UP button and ENTER button for 5 seconds to enable the
superheatsetpointtobechanged.Thesetpointisdisplayedandthe100’s
digitwillblink.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom100’sdigit
tothe10’sdigit.
Pressing the UP button will increase the set point by 10 degrees.
Pressing the DOWN button will decrease the set point by 10 degrees.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom10’sdigit
tothe1’sdigit.
Pressing the UP button will increase the set point by 1 degree.
Pressing the DOWN button will decrease the set point by 1 degree.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom1’sdigit
tothe100’sdigit.
Press and hold UP button and ENTER button for 5 seconds will save the
setpoint.Thedigitswillstopblinking.
LQSP MODE
Press and hold UP button and ENTER button for 5 seconds to enable
the leaving liquid temperature set point to be changed. The set point is
displayedandthe100’sdigitwillblink.
Pressing the UP button will increase the set point by 100 degrees.
Pressing the DOWN button will decrease the set point by 100 degrees.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom100’sdigit
tothe10’sdigit.
Pressing the UP button will increase the set point by 10 degrees.
Pressing the DOWN button will decrease the set point by 10 degrees.
Pressing the ENTERbuttonwillchangetheflashingdigitfrom10’sdigit
tothe1’sdigit.
Pressing the UP button will increase the set point by 1 degree.
Pressing the DOWN button will decrease the set point by 1 degree.
Page 2
Figure 2