7200 Monitor Instruction Manual
26 Technical Specification
26.1 General
Supply Voltage ............................... 85-264VAC, 50/60 Hz,
Power Consumption........................15 VA
Supply Fuse....................................1.6A Anti surge 20 x 5mm (Fitted Internally)
Operating Temperature...................0 to 50°C
Storage Temperature......................-20 to 70°C
Display Resolution..........................0.1%
Response Time...............................0.2 to 120 Seconds (User selectable)
Linearity...........................................(Refer to sensor specification)
Accuracy.........................................(Refer to sensor specification)
Repeatability...................................(Refer to sensor specification)
26.2 Alarm Outputs
Number of Outputs..........................2 SPCO
Alarm Types....................................Low, High, Fault (User configurable)
Operation........................................Fail Safe (De-energised in alarm condition)
Relay Rating....................................5 A @ 230 VAC, 5 A @ 30 VDC
26.3 Analogue Output
Type:...............................................4-20 mA/0-20 mA/0-5 V (User configurable)
Resolution:......................................Better than 0.5%
4-20mA Maximum Output Load:.....1000 Ohms
0-20mA Maximum Output Load:.....1000 Ohms
0-5V Minimum Output Load:...........1000 Ohms
26.4 EMC
EMC:...............................................EN 61000-6-1(2001) EN 61000-6-3(2001)
26.5 Field Mount
Dimensions:....................................160
×
166
×
73 mm (h
×
w
×
d)
Weight:............................................1 Kg
Environmental Rating:.....................IP65
Material:..........................................ABS
Cable Entry:....................................4
×
PG11 (2 factory fitted, 2 supplied separately)
Terminals:.......................................Max conductor cross section 2.5 mm
2
Page 46 of 50 167300IM-Issue 12 Issue Date 14/10/2014