Fig 22: Electronic module LED indicators D-NET
D*%+
%
'(
%
%
%
%&'(%&5'&(%0+(%')&)%1&%'&#)%@%+($&'*'%,5)?1%1)(
LED Indicator
LED Indicator Condition
Description
Left LED
Steady RED
CLOSED indication switch made
“
Flashing RED
Output 1 de-energised, but Closed switch not made
“
Twink RED
Output 1 de-energised, and FTC* timer timed out, input not made
Center LED
Steady GREEN
OPEN indication switch made
“
Flashing GREEN
Output 1 energised, but Open input not made
“
Twink GREEN
Output 1 energised, and FTO* timer timed out, input not made
Right LED
Flashing AMBER
Device On-line but not being communicated with
“
Steady AMBER
Device On-line and communicating
“
Flashing RED
Device senses Bus voltage low
“
Steady RED
Device Bus-Off or Major Internal Fault
“
Flashing RED-AMBER-OFF
Node Beacon function