DIAGNOSTICS
The control records and displays a variety of diagnostic data to
assist with troubleshooting performance issues and fine-tuning
system efficiency. Press the Diagnostics button
from the
Master Settings or Home screens to view the Diagnostic screen.
Figure 26 Diagnostic Screen
Press the screen navigation arrows at the upper-right and
left of the screen to view each diagnostic parameter.
Press the Error Log button
to access the Error Log
(Figure 29) screen. To clear the Error Log, press the Reset
button then the Reset button again on the Clear All Error
Logs screen, then enter "1201" at the password prompt
screen, then press the Accept button to confirm.
Figure 27 Error Log Screen
Press the Home button
to return to the Home screen.
NOTE: If a regeneration occurs while in the Diagnostic screen,
the unit will return to the main screen.
Parameter Description
Flow Rate Displays the current flow rate.
Peak Flow* Displays maximum flow rate of water along
with date and time of occurrence, since last
reset.
Totalizer*
,
** Displays total volume of water used since
last reset.
Last Regen Displays when last regeneration occurred.
Reserve Displays the reserve volume based on the
reserve type selected under master settings.
*This parameter is only available for meter
delayed regeneration type.
Software Version Displays the software version installed on
the controller.
No of Regens Displays how many manually and system
initiated regenerations the system has gone
through since last reset.
Regen Interval Displays the average length of time between
regenerations based on the past four
regenerations.
Daily Usage Displays average water usage for each day of
the week based on the usage on that day for
the past six weeks.
Usage Since Regen Displays water usage since last regeneration.
Last Setting Change Displays the date and time of the last update
to Master Settings.
NOTE*: Only Peak Flow and Totalizer can be changed - they
can be reset to zero.
NOTE**: Totalizer has a maximum value of 99,999,999. If this
number is reached, the Totalizer must be reset to zero
to continue tracking this value.
ALARMS AND ERRORS
If an error in valve or control function occurs, an alarm will
sound and the Home screen will display the Error
Alert button
and the Alarm button .
Figure 28 Alarm and Error Alert
Press the Alarm button to mute the alarm.
Press the Error Alert button to view information about
the error.
Error Alert
Alarm
FLECK 5800/5810/5812 XTRI Service Manual • 15