Operating Manual | Attachment and Installation Cooling Units | Standard Controller (SC) 230 V | 086100113 22/66
3.7 Technical data
3.7.1 Refrigeration circuit
Designation Unit Model DTI / DTS 6201
Cooling capacity at A35 / A35 */** Q
0
W 1150
Cooling capacity at A50 / A35 */** Q
0
W 750
Refrigerant type *
R134a
Refrigerant quantity *
g 400
Temperature setpoint (factory setting)
°C (°F) +35 °C (95 °F)
Fault indication: Switch cabinet interior temperature
(factory setting)
°C (°F) SC-Controller: > +50 °C (+122 °F)
MC-Controller: > +52 °C (+125,6 °F)
Ambient air temperature
°C (°F) +10 … 55 °C (+50 … 131 °F)
Switch cabinet interior temperature
°C (°F) +25 … 45 °C (+77 … 113 °F)
Air volume flow, exterior circuit (free-blowing)
m³/h 885
Air volume flow, interior circuit (free-blowing)
m³/h 885
Tab. 5: Refrigeration data model DTI / DTS 6201
Designation Unit Model DTI / DTS 6301
Cooling capacity at A35 / A35 */** Q
0
W 1550
Cooling capacity at A50 / A35 */** Q
0
W 1200
Refrigerant type *
R134a
Refrigerant quantity *
g 350
Temperature setpoint (factory setting)
°C (°F) +35 °C (95 °F)
Fault indication: Switch cabinet interior temperature
(factory setting)
°C (°F) SC-Controller: > +50 °C (+122 °F)
MC-Controller: > +52 °C (+125,6 °F)
Ambient air temperature
°C (°F) +10 … 55 °C (+50 … 131 °F)
Switch cabinet interior temperature
°C (°F) +25 … 45 °C (+77 … 113 °F)
Air volume flow, exterior circuit (free-blowing)
m³/h 885
Air volume flow, interior circuit (free-blowing)
m³/h 885
Tab. 6: Refrigeration data model DTI / DTS 6301
* Data on the type plate.
** The use of optional filter mats reduces the cooling capacity