IntelliVue Telemetry System Specifications
IntelliVue Telemetry System Infrastructure Installation and Service Guide 1-25
Table 1-13: UPS Specifications
UPS
Requirements
Parameter Specification
Input Voltage 1.4 GHz ITS 2.4 GHz ITS
120VAC +/-10% 100, 120, 127, 220, 240 VAC ± 10%
Input
Frequency
60Hz +/-3Hz minimum 50, 60Hz +/-3Hz
UPS AC
Input Port
100, 120VAC model: one NEMA 5-15P plug.
230 VAC model: one IEC 320 C14 plug.
Number of UPS
AC output ports
100, 120VAC model: 3 minimum (NEMA 5-15R output receptacles),
desirable to have 5 ports or greater.
230V model: 3 minimum (IEC 320 C13 output receptacles), desirable
to have 5 ports or greater.
Power delivery UPS shall provide at least 225Watts for >
90 seconds to power
12 APs, 1 Sync Unit, 2 APC, 1 POE, & 1 Switch from one UPS unit with 5
UPS ports.
Or:
12 APs, 1 Sync Unit, 1 APC, 1 POE, from one UPS unit with 3 UPS ports.
Additional UPS would be needed to power redundant APC & Switch.
Power Fail
Transition
UPS must be responsive to power fail conditions such that ITS system
does not experience reboot due to transition to temporary battery
backup power.
Power Fail Alert UPS shall provide local auditory response to power fail conditions.
EMI Filtering Provide AC line EMI filtering over 100KHz to 30MHz on UPS ports.
EMC FCC part 15 class A or B certification, CE Mark: CISPR 22/ EN 55022,
and CISPR 24 / EN 55024.
Safety UL certification, EN 62040 (Low Voltage Directive).
Mounting Rack Mounting is desirable.