8.3.4. Preset Multiple Registers (Function code 10H)
Preset Registers Format
(MasterSPM33)
Response Format
(SPM33Master)
Unit ID/ Slave address 1 byte Unit ID/ Slave address 1 byte
10 H (Function Code) 1 byte 10 H (Function Code) 1 byte
Start register address 2 bytes Start register address 2 bytes
Register num. 2 bytes Register num. 2 bytes
Byte num.
(2 * register num.)
1 byte CRC check code 2 bytes
First register data
Second register data
...
CRC check code 2 bytes
This command packet allows the Master to program the SPM33 setup
parameters.
Note: SPM33 presume all registers are continuous from the first one.