EasyManua.ls Logo

Pilot Communications SPM33 - Preset Multiple Registers (Function Code 10 H)

Pilot Communications SPM33
78 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.3.4. Preset Multiple Registers (Function code 10H)
Preset Registers Format
(MasterSPM33)
Response Format
(SPM33Master)
Unit ID/ Slave address 1 byte Unit ID/ Slave address 1 byte
10 H (Function Code) 1 byte 10 H (Function Code) 1 byte
Start register address 2 bytes Start register address 2 bytes
Register num. 2 bytes Register num. 2 bytes
Byte num.
(2 * register num.)
1 byte CRC check code 2 bytes
First register data
Second register data
...
CRC check code 2 bytes
This command packet allows the Master to program the SPM33 setup
parameters.
Note: SPM33 presume all registers are continuous from the first one.
37

Related product manuals