8.6.2 List of demand data registers
Regist
er
addres
s
Read
/write
attrib
ute
Definition Data
type
Description
40701 RO Phase A current demand UINT16 Calculation factor:
0.001, unit: A
40702 RO Phase B current demand
40703 RO Phase C current demand
40704 RO Phase A active power demand UINT16 Calculation factor:
0.1, unit: W
40705 RO Phase B active power demand
40706 RO Phase C active power demand
40707 RO Total active power demand low word LINT32 Calculation factor:
0.1, unit: W
40708 Total active power demand high word
40709 RO Maximum phase A current demand UINT16 Calculation factor:
0.001, unit: A
40710 RO Maximum phase B current demand
40711 RO Maximum phase C current demand
40712 RO Maximum phase A active power Calculation factor:
52