40218 Reserved
40219 Reserved
40220 Reserved
40221
RW Operation value of
voltage upper limit
Calculation factor: 0.01, Unit:V
0 means closed
For 110V – 500V, default 0.
40222
RW Action time of voltage
upper limit
0-120s。
40223
RW Operation value of
voltage lower limit
Calculation factor: 0.01, Unit:V
0 means closed
For 110V – 500V, default 0.
40224
RW Action time of voltage
lower limit
0-120s。
40225
RW
Operation value of
current upper limit (low
word)
Primary value of current.
Calculation factor: 0.1, Unit: A
0 means closed
1.0A-60000.0A
40226
Operation value of
current upper limit (high
61