40233
RW Operation value of
frequency lower limit
Calculation factor: 0.01,
Unit: Hz
0 means closed
45Hz – 65Hz
40234
RW Action time of frequency
lower limit
0-120s
40235
RW Operation value of active
power upper limit (low
word)
Primary side value
Calculation factor: 0.1,
Unit: kW
0.1-40000.0kW
40236
Operation value of active
power upper limit (high
word)
40237
RW Action time of active
power upper limit
0-120s
40238
RW Setting for phase loss
alarm
0 means closed
1 means open
When phase A or phase B < 110V,
it means phase loss.
63