P2HZ X1
Operating Manual P2HZ X1
20124-EN-09
| 17
Relay outputs 774330 774332 774340
Utilisation category of
safety contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 1250 VA 1250 VA 1250 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 125 W 125 W 125 W
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 500 VA 500 VA 500 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 50 W 50 W 50 W
Utilisation category
in accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 2,5 A 2,5 A 2,5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 1,5 A 1,5 A 1,5 A
Utilisation category of
auxiliary contacts
AC15 at 230 V 230 V 230 V
Max. current 2 A 2 A 2 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 1,5 A 1,5 A 1,5 A
Utilisation category in ac-
cordance with UL
Voltage 240 V AC G. P. 240 V AC G. P. 240 V AC G. P.
with current 5 A 5 A 5 A
Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive
with current 5 A 5 A 5 A
Pilot Duty C300, R300 C300, R300 C300, R300