EasyManuals Logo

Pilz P2HZ X1 User Manual

Pilz P2HZ X1
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
P2HZ X1
Operating Manual P2HZ X1
20124-EN-09
| 17
Relay outputs 774330 774332 774340
Utilisation category of
safety contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 1250 VA 1250 VA 1250 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 5 A 5 A 5 A
Max. power 125 W 125 W 125 W
Utilisation category of
auxiliary contacts
AC1 at 240 V 240 V 240 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 500 VA 500 VA 500 VA
DC1 at 24 V 24 V 24 V
Min. current 0,01 A 0,01 A 0,01 A
Max. current 2 A 2 A 2 A
Max. power 50 W 50 W 50 W
Utilisation category
in accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Utilisation category of
safety contacts
AC15 at 230 V 230 V 230 V
Max. current 2,5 A 2,5 A 2,5 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 1,5 A 1,5 A 1,5 A
Utilisation category of
auxiliary contacts
AC15 at 230 V 230 V 230 V
Max. current 2 A 2 A 2 A
DC13 (6 cycles/min) at 24 V 24 V 24 V
Max. current 1,5 A 1,5 A 1,5 A
Utilisation category in ac-
cordance with UL
Voltage 240 V AC G. P. 240 V AC G. P. 240 V AC G. P.
with current 5 A 5 A 5 A
Voltage 24 V DC Resistive 24 V DC Resistive 24 V DC Resistive
with current 5 A 5 A 5 A
Pilot Duty C300, R300 C300, R300 C300, R300

Other manuals for Pilz P2HZ X1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pilz P2HZ X1 and is the answer not in the manual?

Pilz P2HZ X1 Specifications

General IconGeneral
BrandPilz
ModelP2HZ X1
CategoryRelays
LanguageEnglish

Related product manuals