PKB-M, PKB-MS Operating Manual 15
ENGLISH
Display menus
Monitor
Function monitoring
Values can not be changed within these menus!
in Proc.
XXXXXXXX
Process
XXXXXXXX:
Init! Initialisation
Error? Temperature test
Driving? Waiting for the start contact to open (motor on)
Stop? Waiting for the start contact to close (motor off)
Tv1 Safety time t
v1
Tv2 Safety time t
v2
Ramp Run-up of the current control
Ignition Braking operation with set current set value (control) or firing
time point (without control)
Tv3 Safety time t
v3
Tv4 Safety time t
v4
The control logic processes the signals in this order.
BreakCon
XXXXXXXX
Brake interrupt
XXXXXXXX
None No brake interrupt (e.g. by switching on the unit)
TimeOut Set braking time ended
Man.Stop Braking process interrupted by opening the start contact
Aut.Stop Standstill detected automatically (operation with automatic
standstill detection)
Int.Temp Permitted heatsink temperature exceeded
Ext.Temp Permitted (external) motor temperature exceeded
Overload Permitted braking current exceeded
OvLd-tv1 Permitted braking current exceeded during t
v1
OvLd-tv2 Permitted braking current exceeded during t
v2
OvLd-Rmp Permitted braking current exceeded during the run-up ramp
time
OvLd-Ign Permitted braking current exceeded during the braking process
Watchdog Internal error