PNOZ s9
Operating Manual PNOZ s9
21401-EN-10
25
Safety characteristic data
NOTICE
You must comply with the safety-related characteristic data in order to
achieve the required safety level for your plant/machine.
Operating
Mode
EN ISO
13849-1:
2015
PL
EN ISO
13849-1:
2015
Category
EN 62061
SIL CL
EN 62061
PFH
D
[1/h]
IEC 61511
SIL
IEC 61511
PFD
EN ISO
13849-1:
2015
T
M
[year]
Safety con-
tacts,
delayed
PL e Cat. 4 SIL CL 3 2,34E-09 SIL 3 2,75E-05 20
All the units used within a safety function must be considered when calculating the safety
characteristic data.
INFORMATION
A safety function's SIL/PL values are not identical to the SIL/PL values of
the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.