Relay outputs
Utilisation category of safety contacts
AC1 at 240 V
Min. current 0,01 A
Max. current 6 A
Max. power 1500 VA
DC1 at 24 V
Min. current 0,01 A
Max. current 6 A
Max. power 150 W
Utilisation category
In accordance with the standard EN 60947-5-1
Utilisation category of safety contacts
AC15 at 230 V
Max. current 5 A
DC13 (6 cycles/min) at 24 V
Max. current 4 A
Utilisation category in accordance with UL
Voltage 240 V AC G. P.
With current 6 A
Voltage 24 V DC Resistive
With current 6 A
Pilot Duty C300, R300
External contact fuse protection, safety contacts
In accordance with the standard EN 60947-5-1
Max. melting integral 240 A²s
Blow-out fuse, quick 6 A
Blow-out fuse, slow 4 A
Blow-out fuse, gG 6 A
Circuit breaker 24V AC/DC, characteristic B/C 4 A
Conventional thermal current 6 A
Contact material AgSnO2 + 0,2 µm Au
Times
Switch-on delay
With monitored start typ. 45 ms
With monitored start max. 70 ms
Delay-on de-energisation
With E-STOP typ. 15 ms
With E-STOP max. 30 ms
With power failure typ. 70 ms
With power failure max. 110 ms
Recovery time at max. switching frequency 1/s
After E-STOP 50 ms
After power failure 150 ms
Waiting period with a monitored start 180 ms
Min. start pulse duration with a monitored start 30 ms