16 - ATR227 - User manual
WXQ(
Tune (impulsive digital input). Parameter 8
3LG
must be set as
0$Q
$X0$
Automatic/Manual
$FWW
Regulation type
RU6W
Output reset (impulsive digital input)
26
GLFW Digital Input Contact Type (Password 1234)
Select the digital input inactive contact.
RF
Open contact (Default)
FF
Closed contact
27
$/ Alarm 1 (Password 1234)
Alarm 1 selection.
GLV
Disabled (Default)
$$/
Absolute / threshold, referring to process
E$/
Band alarm
+G$/
Upper deviation alarm
/G$/
Lower deviation alarm
28
$, R Alarm 1 State Output (Password 1234)
Alarm 1 output contact and intervention type
QRV
(N.O. Start) Normally open, active at start (Default)
QFV
(N.C. Start) Normally closed, active at start
QRW
(N.O. Threshold) Normally open, active on reaching alarm
1
QFW
(N.C. Threshold) Normally closed, active on reaching alarm
1
29 D+\ Alarm 1 Hysteresis (Password 1234)
-99.9..99.9 °C/°F. Default: 0.5.°C
30 D/G Alarm 1 Led (Password 5678)
Denes the state of A1 led corresponding to the relative contact
RF
ON with open contact
FF
ON with closed contact (Default)
31
DVH Alarm 1 State Error (Password 5678)
State of contact for alarm 1 output in case of error.
RF
Open contact (Default)
FF
Closed contact
32
DVS Alarm 1 Setpoint Protection (Password 1234)
Does not allow the user to modify setpoint.
IUHH
Modiable by the user (Default)
/RFN
Locked
+LGH
Locked and hidden
1
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm
condition reappers, after that it was restored.