33 D U H Alarm 1 Reset (Password 5678)
Type of Reset for contact of alarm 1.
DUH
Automatic Reset (Default)
PUH
Manual reset
SET
PUHV
Manual Reset Stored (keeps relay status also after an eventual power
failure)
34 DGH Alarm 1 Delay (Password 5678)
-900..+900 seconds. Default: 0.
Negative: delay in alarm output phase
Positive: delay in alarm entry phase.
35
$/ Alarm 2 (Password 1234)
Alarm 2 selection.
GLV
Disabled (Default)
$$/
Absolute / threshold, referring to process
E$/
Band alarm
+G$/
Upper deviation alarm
/G$/
Lower deviation alarm
36
$ R Alarm 2 State Output (Password 1234)
Alarm 2 output contact and intervention type.
QRV
(N.O. Start) Normally open, active at start (Default)
QFV
(N.C. Start) Normally closed, active at start
QRW
(N.O. Threshold) Normally open, active on reaching alarm
2
QFW
(N.C. Threshold) Normally closed, active on reaching alarm
2
37 D+\ Alarm 2 Hysteresis (Password 1234)
-99.9..99.9 °C/°F. Default: 0.5.°C
38 D/G Alarm 2 Led (Password 5678)
Denes the state of A2 led corresponding to the relative contact
RF
ON with open contact
FF
ON with closed contact (Default)
39
DVH Alarm 2 State Error (Password 5678)
State of contact for alarm 2 output in case of error
RF
Open contact(Default)
FF
Closed contact
2
On activation, the output is inhibited if the controller is in alarm mode. Activates only if alarm
condition reappers, after that it was restored.