18 - ATR227 - User manual
40 DVS Alarm 2 Setpoint Protection (Password 1234)
Does not allow the user to modify setpoint
IUHH
Modiable by the user (Default)
/RFN
Locked
+LGH
Locked and hidden
41
DUH Alarm 2 Reset (Password 5678)
Type of Reset for contact of alarm 2.
DUH
Automatic Reset (Default)
PUH
Manual reset
SET
PUHV
Manual Reset Stored (keeps relay status also after an eventual power
failure)
42 DGH Alarm 2 Delay (Password 5678)
-900..+900 seconds. Default: 0.
Negative: delay in alarm output phase
Positive: delay in alarm entry phase.
48
S E Proportional Band (Password 5678)
Process intertia in °C/°F.
0 ON / OFF if t.i. is equal to 0 (Default)
1-9999 °C/°F
49
LW Integral Time (Password 5678)
Process inertia in seconds.
0.0-999.9 secondi (0 = integral disabled), Default 0.0
50
GW Derivative Time (Password 5678)
Normally ¼ of integral time.
0.0-999.9 seconds (0 = derivative disabled), Default 0.0
51
GE Dead Band (Password 5678)
0-1000 [digit1] (degrees.tenths for temperature sensors) (Default: 0)
52 F W Cycle Time (Password 5678)
(for P.I.D. on remote control switch 15 sec., for P.I.D. on SSR 1 sec.)
1-300 seconds (Default:15s), If par.6
FRXW
is set as
F66U
(Default:2s)
53
// R 3 Lower Limit Output Percentage (Password 5678)
Selects min. value for command output percentage.
0..100%, Default: 0%.
54
8/ R S Upper Limit Output Percentage (Password 5678)
Selects max. value for command output percentage.
0 – 100%, Default: 100%.