10 - DRR244 - User manual
5.1 Wiring diagram
DRR244-13ABC-T
24 23 22
24...230V
AC/DC
B (+)
RS485
CT
PT100
TC
NI100 A\V
PTC
NTC
A (-) DO2
(PNP)
DI2
(PNP)
DI1
(PNP)
+V
21 20 19
1
NO C
Q1 Q2
Q3
NC NO NO 0V (PNP)
DO1
AO1
V/mA
C CNC
2 3 4 5 6 7 8 9 10 11 12
18 17 16 15 14 13
5.1.a Power Supply
SUPPLY
24...230
VAC/DC
24
23
Switching power supply 24..230 VAC/VDC ±15% 50/60 Hz - 9 Watt/VA.
Galvanic insulation (2500V).
5.1.b Analogue Input AI1
AI1
TC
Shield/Schermo
13
14
For thermocouples K, S, R, J, T, E, N, B.
Comply with polarity
For possible extensions, use compensated cable and terminals suitable for
the thermocouples used (compensated).
When shielded cable is used, it should be grounded at one side only.
AI1
PT/NI100
Shield/Schermo
Rosso
Red
Bianco
White
Rosso
Red
13
14
15
For thermoresistances PT100, Ni100.
For the three-wire connection use wires with the same section.
For the two-wire connection short-circuit terminals 13 and 15
When shielded cable is used, it should be grounded at one side only.
RED/ROSSO
RED/ROSSO
WHITE/BIANCO
AI1
Shield/Schermo
PTC/NTC
15
14
For thermoresistances NTC, PTC, PT500, PT1000 and linear potentiome-
ters.
When shielded cable is used, it should be grounded at one side only to avoid
ground loop currents.
AI1
V
mA
+V
Shield/Schermo
16
14
13
For linear signals in Volt and mA
Comply with polarity
When shielded cable is used, it should be grounded at one side only to
avoid ground loop currents.
Its possible to select +V at 12Vdc or 24Vdc, by configuring parameter 282
V.out (GROUP R - di SP. - Display and interface).